A – earthing conductor cross section in mm 2
I – rms current in kA
TCAP – thermal capacity per unit volume
tc – duration of current in s
αr – thermal coefficient of resistivity
ρr – resistivity of the ground conductor
Ko – thermal coefficient (1/ αr) – Tr in °C
Tm – maximum allowable temperature °C
Ta – ambient temperature
Product name | Metal conductivity in % | Thermal coefficient od resistivity αr at 20 (1/ °C) | Thermal coefficient Ko at 0 °C (0°C) | Maximum allowable temperature Tm in °C | Resistivity of the ground conductor ρr at 20°Cin | TCAP – thermal capacity per unit volume |
Copper-bonded tape Fe/C u 250 µ m | 18 | 0.003 78 | 245 | 1084 | 9,64 | 3.38 |
Copper-bonded tape Fe/C u 70 µ m | 18 | 0.003 78 | 245 | 1084 | 9,64 | 3.38 |
Copper/tin-bonded tape St/Cu 70 µ m/Sn 3 µ m | 18 | 0.003 78 | 245 | 1084 | 9,64 | 3.85 |
Copper tape Cu | 97 | 0,00 381 | 245 | 1084 | 1,78 | 3,42 |
Stainless steel 304 tape | 2,4 | 0,00 130 | 749 | 1400 | 72 | 4,03 |
Zink coated tape | 8.8 | 0.003 20 | 293 | 419 | 20.10 | 3.93 |
Cross-sectional area of the earth coductor in mm2 | Type of tape / tape dimensions | Weight of 1 m steel tape with St/Cu, St/Cu/Sn lub Zn | Weight of 1 m copper tape | Weight of 1 m Stainless steel 304 tape |
from 50 to 78,93 | 25,14 x 3,14 | 0,62 | 0,67 | 0,6 |
from 78,93 to 94,63 | 30,14 x 3,14 | 0,72 | 0,80 | 0,72 |
from 94,63 to 104,07 | 25,14 x 4,14 | 0,81 | 0,89 | 0,8 |
from 104,07 to 124,77 | 30,14 x 4,14 | 0,98 | 1,07 | 0,96 |
from 124,77 to 166,17 | 40,14 x 4,14 | 1,30 | 1,42 | 1,28 |
from 166,17 to 206,31 | 40,14 x 5,14 | 1,62 | 1,78 | 1,6 |
from 206,31 to 257,72 | 50,14 x 5,14 | 2,02 | 2,23 | 2 |
from 257,72 to 309,12 | 60,14 x 5,14 | 2,42 | 2,67 | 2,4 |