CBM Technology

Type a product name, catalogue number, document name or topic. Letter case and accents do not matter.

We search

  • Products
  • Catalogue numbers
  • Documents
  • Calculators
  • Technical knowledge

For example

Contact
CBM / DESIGN ZONE

CBM Dom calculator

Draw the building outline and place the connection leads and vertical rods. Count the St/Cu wire, joints and cost.

OUTLINE AND MATERIALS

Your CBM Dom design

Choose an outline or draw one on the grid. You can change the dimensions with the mouse or in the fields.

Foundation slab
Slab reinforcement in contact with the soil acts as a foundation earth electrode. In the slab concrete a Ø 8 mm St/Cu wire loop is joined to the reinforcement and the leads connect it to the ring earth. The resistance is calculated from the vertical rods alone.
A Ø 8 mm St/Cu wire loop in the slab concrete, joined to the reinforcement with black steel clamps. The leads connect it to the ring earth.
Corners first, because lightning protection down conductors run there. Any extra leads go on the longest walls.
In addition to the section between the ring earth and the wall. Include the vertical run and the route to the clamp.
Ring earth and lead material
Copper-bonded wire Ø 8 mm St/CuC1110249(60M)METRCBM recommends Ø 8 mm St/Cu wire: it is permitted by PN-EN IEC 62561-2 and PN-HD 60364-5-54 (CBM article 06.2026).
TOP VIEW / 1 m GRID

Building outline and ring earth

Drag a corner. Click a wall to change its length.

4 points
X1 · 16.0 mY1 · 12.0 mX2 · 16.0 mY2 · 12.0 mL1L2L3L4P1P2P3P4
Building Ring earth of Ø 8 mm St/Cu wire Earthing conductor (lead) of Ø 8 mm St/Cu wire Vertical rod Ø 14.2 mm Loop of Ø 8 mm St/Cu wire joined to the reinforcement with black steel clamps

Wall dimensions

X marks horizontal walls in the drawing, Y vertical ones, S slanted ones. Type a length and press Enter: the wall end and the next corner move along it.

  • m
  • m
  • m
  • m
02Side sectionNon-insulated slab: ring earth, loop in the slab and vertical rods
DIAGRAM · NOT TO SCALE
BUILDINGwidth 12.0 mMETPENGround level ±0.002 rods2 rodsL = 3.0 mConnection lead of Ø 8 mm St/Cuwire from the ring to the clampMain earthing terminal (MET)connected to the loopat at least two cornersØ 8 mm St/Cu wireØ 8 mm St/Cu wire in the concretelaid as a loop, joined to thereinforcement with blacksteel clampsSlab with reinforcementin contact with the soilØ 8 mm St/Cu earthing conductorjoining the loop in the concreteto the ring, at leastat two cornersConcrete bedor native soilRing earth: wire Ø 8 mm St/Cu1.0 m from the building,around the whole buildingVertical rodØ 14.2 mmSOIL · ρ = 100 Ω·mCross-section of the building: all rods from the top view, with the number of rods standing behind one another.
Ring earth at least 0.5 m below ground (EN 62305-3): dots in the section, the line is the rest of the ring around the building Connection lead of Ø 8 mm St/Cu wire from the ring to the clamp Ø 8 mm St/Cu wire loop in the concrete, joined to the reinforcement and by earthing conductors to the ring Vertical rod Ø 14.2 mm Main earthing terminal (MET) connected to the loop with Ø 8 mm St/Cu wire at at least two corners PEN conductor to the MET (symbolic) Concrete bed or native soil
VERTICAL RODS4 × 3.0 mRING FROM BUILDING1.0 mSLABnot insulated
VERTICAL RODS OR RING EARTH ONLY

Earth resistance

Non-insulated slab
Don’t know the soil resistivity? Measure it with the Wenner method (optional)
On the ring earth, corners first, then in the middle of the longest walls.
Recommended by PN-EN 62305: 10 Ω.
Vertical rod depth
1. Rod section length
2. Rod depth: a multiple of the 1 m section
Forged Ø 14.2 mm rod made of sections of one length: all 1 m (houses) or all 1.5 m, up to 7 m.
VERTICAL RODS, WITHOUT THE RING
8.5 Ω
The rods meet 10.0 Ω
One rod 3.0 m34.13 ΩRods 4 × 3.0 m8.53 ΩArea inside the ring252.0 m² · re 9.0 m
  • The result is the resistance of the vertical rods alone: R of one rod / n. With a combined electrode the ring and other horizontal electrodes are not included, because in practice the rods decide (agreed with CBM). The ring earth is calculated only when there are horizontal electrodes alone.
  • The minimum distance between rods is 4 m (source: CBM comic, in Polish).
  • Slab reinforcement is not included in the resistance, so the result is conservative.
RING EARTH AND LEADS INCLUDING RESERVE
85.5 m
Quantities from geometry
Ring earth length64.0 mConnection leads13.7 mOutline area192.0 m²
NET COST COMPARISON

Ø 8 mm St/Cu wire or galvanized tape?

The same length from your project: 85.5 m (ring earth, leads and reserve). Wire is priced per metre, tape per kilogram, as on the market.

COPPER-BONDED WIRE

Ø 8 mm St/Cu

enter a price

Length
85.5 m
Mass
35 kg
Net price
—
GALVANIZED TAPE

30 × 4 mm

enter a price

Length
85.5 m
Mass
85 kg
Net price
—
DIFFERENCE

Enter both net prices.

Mass: wire 35 kg, tape 85 kg.

1 kg of Ø 8 mm St/Cu wire = 2.43 m, 1 kg of 25 × 4 mm tape = 1.27 m, 1 kg of 30 × 4 mm tape = 1 m

Conversion: Ø 8 mm St/Cu copper-bonded wire and galvanized 25 × 4 mm tape per the CBM slide (10.2026), galvanized 30 × 4 mm tape per the CBM article (06.2026). Mass is counted in whole kilograms. You enter the prices yourself; current prices are available from CBM. According to the CBM article (06.2026), an earth electrode made of Ø 8 mm St/Cu copper-bonded wire can last up to 20 years longer in the soil than galvanized tape.

Materials and cost

CBM products
ItemQuantityNet price [EUR]
Copper-bonded wire Ø 8 mm St/Cu: ring earth and leads from the ring to the clampC1110249(60M)METR · Drut St/Cu;0,070mm Cu;fi 8mm;60m · length to order · mass in whole kg85.5 m · 35 kg
Copper-bonded wire Ø 8 mm St/Cu: loop in the slab joined to the reinforcementC1110249(60M)METR · 1.0 m from the building edge: loop 48.0 m + reserve52.8 m · 21 kg
Copper-bonded wire Ø 8 mm St/Cu: loop–ring conductorsC1110249(60M)METR · 4 × sloped from the slab loop to the ring: 11.5 m + reserve12.7 m · 5 kg
Oblique clamp wire Ø 8 / wire Ø 8, stainless steelC1030476N Uchwyt skośny,drut fi8/fi8,stal nierdz.;M8zamkowa · at the ring: 1 × ring closure, 4 × lead from the ring to the clamp, 4 × loop–ring conductor · at the loop: 4 × loop–ring conductor, 1 × loop closure · proposal to be confirmed by CBM14 pcs
Forged earth rod 14.2 mm / 1 mC0000171C100 · 4 × 3.0 m: 3 × 1 m sections per rod12 pcs
Oblique clamp rod 14.2 / wire Ø 8, stainless steelC1030477N Uchwyt skośny,uz.14,2/drut fi8,stal nierdz;M8zamko · 1 per rod (rod–ring) · proposal to be confirmed by CBM4 pcs
Oblique clamp wire / reinforcing bar, black steelC1030475S Uchwyt skośny drut/bed.,pręt zbr.;stal;M8 zamkowa · 24 loop–reinforcement (every 2 m of the loop, PN-EN 62305-3:2025)24 pcs
CBM insulating tape for underground joints, 30 mm × 10 mC1030355 · 1 roll per 4 clamps in the soil: 9 × C1030476N at the ring + 4 × C1030477N rod–ring · Insulating tape for an earthing clamp in the soil. The tape prevents stress corrosion, which occurs when two factors act together: a corrosive environment (the soil) and a constant tensile force on the clamp plates from the tightened bolts. Removing the corrosive environment prevents stress corrosion.4 pcs
Driving head for forged rod 14.2 and 16 mm, SDS-Max (optional)C1090375 Bijak do uziomu kut.;14,2mm i 16mm;SDS-Max · for an SDS-Max hammer1 pcs
Driving pin for forged rod 14.2 mm (optional)C1080375 Trzpień do uziomu kutego;14,2mm1 pcs
Stabiliser for forged rod 14.2 mm (optional)C1070375 Stabilizator do uziomu kutego;14,2mm1 pcs
Total St/Cu wire Ø 8C1110249(60M)METR · sum of the 3 wire rows above (no separate price)151.0 m · 61 kg
Net prices: wire per metre, other items per piece. Wire mass in whole kilograms. Loop–reinforcement clamps every 2 m of the loop (PN-EN 62305-3:2025); other clamp counts (breakdown in the row notes) are a proposal to be confirmed by CBM.
Pricing incomplete
i

Quantity plan: the ring earth is an offset of the outline sides with square corners. The joint count assumes a closed wire loop and one connection per connection lead. Resistance is an estimate for uniform soil: with vertical rods the result is the rods alone (BS 7430), without rods the ring alone R = 0.6·ρ/√A (CBM article, consistent with DEHN). Cutting plan, additional joints, material selection and soil conditions must be checked in the design, and the resistance must be confirmed by measurement. The tool does not confirm compliance with standards.

CBM DOM CALCULATOR · PLAN AND RESISTANCE

Non-insulated slab

Date
Resistance: vertical rods8.5 ΩOne rod 3.0 m: 34.13 Ω · 4 × 3.0 m: 8.53 ΩMeets 10.0 Ω
Foundation slab
not insulated
Building outline
192.0 m² · 56.0 m
Ring earth
64.0 m · A = 252.0 m²
Distance from building
1.0 m
Loop in the slab
48.0 m · 1.0 m from the edge
Ring earth material
copper-bonded wire Ø 8 mm St/Cu · 85.5 m
Connection leads
4 pcs · +2.0 m
Material reserve
10%
Soil resistivity ρ
100.0 Ω·m
Vertical rods
4 × 3.0 m (3 × 1 m) · Ø 14.2 mm
Required resistance
10.0 Ω
Top view1 m grid · ring earth 1.0 m from the building wall · building wall dimensions
X1 · 16.0 mY1 · 12.0 mX2 · 16.0 mY2 · 12.0 mL1L2L3L4
Building Ring earth of Ø 8 mm St/Cu wire Earthing conductor (lead L) of Ø 8 mm St/Cu wire Vertical rod Ø 14.2 mm Loop of Ø 8 mm St/Cu wire joined to the reinforcement with black steel clamps

ROT = 0,6 · ρ / √A (M. Łoboda, R. Marciniak, CBM article 06.2026, Table 1; consistent with DEHN, tab. 5.5.1) · Rr = ρ / (2πL) · [ln(8L/d) − 1] (BS 7430:2011, cl. 9.5.3, d = 14.2 mm) · result = Rr / n, the rods alone: with a combined electrode the ring and horizontal electrodes are not included (agreed with CBM); the ring is calculated only without rods.

Slab reinforcement is not included in the resistance. Preliminary calculation for uniform soil; the result must be checked in the design and by measurement after installation. Schematic drawing, dimensions come from the parameters.

CBM DOM CALCULATOR · SIDE SECTION

Non-insulated slab

Date
02Side sectionNon-insulated slab: ring earth, loop in the slab and vertical rods
DIAGRAM · NOT TO SCALE
BUILDINGwidth 12.0 mMETPENGround level ±0.002 rods2 rodsL = 3.0 mConnection lead of Ø 8 mm St/Cuwire from the ring to the clampMain earthing terminal (MET)connected to the loopat at least two cornersØ 8 mm St/Cu wireØ 8 mm St/Cu wire in the concretelaid as a loop, joined to thereinforcement with blacksteel clampsSlab with reinforcementin contact with the soilØ 8 mm St/Cu earthing conductorjoining the loop in the concreteto the ring, at leastat two cornersConcrete bedor native soilRing earth: wire Ø 8 mm St/Cu1.0 m from the building,around the whole buildingVertical rodØ 14.2 mmSOIL · ρ = 100 Ω·mCross-section of the building: all rods from the top view, with the number of rods standing behind one another.
Ring earth at least 0.5 m below ground (EN 62305-3): dots in the section, the line is the rest of the ring around the building Connection lead of Ø 8 mm St/Cu wire from the ring to the clamp Ø 8 mm St/Cu wire loop in the concrete, joined to the reinforcement and by earthing conductors to the ring Vertical rod Ø 14.2 mm Main earthing terminal (MET) connected to the loop with Ø 8 mm St/Cu wire at at least two corners PEN conductor to the MET (symbolic) Concrete bed or native soil
VERTICAL RODS4 × 3.0 mRING FROM BUILDING1.0 mSLABnot insulated

Net cost comparison: copper-bonded wire and galvanized tape

MaterialLengthMassNet price [EUR]Net cost [EUR]
copper-bonded wire Ø 8 mm St/Cu85.5 m35 kg
galvanized tape 30 × 4 mm85.5 m85 kg

1 kg of Ø 8 mm St/Cu wire = 2.43 m, 1 kg of 25 × 4 mm tape = 1.27 m, 1 kg of 30 × 4 mm tape = 1 m. Mass in whole kilograms. Wire is priced per metre, tape per kilogram; the designer enters net market prices.

Bill of materials

Quantities are a geometric suggestion; cutting plan, joints and fittings are agreed in the design. The designer enters net prices; current prices are available from CBM.

ItemCatalogue no.QuantityNet price [EUR]Net value [EUR]
Copper-bonded wire Ø 8 mm St/Cu: ring earth and leads from the ring to the clampC1110249(60M)METR · Drut St/Cu;0,070mm Cu;fi 8mm;60m · length to order · mass in whole kgC1110249(60M)METR85.5 m · 35 kg
Copper-bonded wire Ø 8 mm St/Cu: loop in the slab joined to the reinforcementC1110249(60M)METR · 1.0 m from the building edge: loop 48.0 m + reserveC1110249(60M)METR52.8 m · 21 kg
Copper-bonded wire Ø 8 mm St/Cu: loop–ring conductorsC1110249(60M)METR · 4 × sloped from the slab loop to the ring: 11.5 m + reserveC1110249(60M)METR12.7 m · 5 kg
Oblique clamp wire Ø 8 / wire Ø 8, stainless steelC1030476N Uchwyt skośny,drut fi8/fi8,stal nierdz.;M8zamkowa · at the ring: 1 × ring closure, 4 × lead from the ring to the clamp, 4 × loop–ring conductor · at the loop: 4 × loop–ring conductor, 1 × loop closure · proposal to be confirmed by CBMC1030476N14 pcs
Forged earth rod 14.2 mm / 1 mC0000171C100 · 4 × 3.0 m: 3 × 1 m sections per rodC0000171C10012 pcs
Oblique clamp rod 14.2 / wire Ø 8, stainless steelC1030477N Uchwyt skośny,uz.14,2/drut fi8,stal nierdz;M8zamko · 1 per rod (rod–ring) · proposal to be confirmed by CBMC1030477N4 pcs
Oblique clamp wire / reinforcing bar, black steelC1030475S Uchwyt skośny drut/bed.,pręt zbr.;stal;M8 zamkowa · 24 loop–reinforcement (every 2 m of the loop, PN-EN 62305-3:2025)C1030475S24 pcs
CBM insulating tape for underground joints, 30 mm × 10 mC1030355 · 1 roll per 4 clamps in the soil: 9 × C1030476N at the ring + 4 × C1030477N rod–ring · Insulating tape for an earthing clamp in the soil. The tape prevents stress corrosion, which occurs when two factors act together: a corrosive environment (the soil) and a constant tensile force on the clamp plates from the tightened bolts. Removing the corrosive environment prevents stress corrosion.C10303554 pcs
Driving head for forged rod 14.2 and 16 mm, SDS-Max (optional)C1090375 Bijak do uziomu kut.;14,2mm i 16mm;SDS-Max · for an SDS-Max hammerC10903751 pcs
Driving pin for forged rod 14.2 mm (optional)C1080375 Trzpień do uziomu kutego;14,2mmC10803751 pcs
Stabiliser for forged rod 14.2 mm (optional)C1070375 Stabilizator do uziomu kutego;14,2mmC10703751 pcs
Total St/Cu wire Ø 8sum of the 3 wire rows above (no separate price)C1110249(60M)METR151.0 m · 61 kg
No complete price